Safety Electromagnetic Flow Meter 20mA PTFE PFA F46 Liner Material DN200-DN400 EMF Flow Meter

Basic Properties
Place of Origin: Jiangsu, China
Brand Name: INSTE
Model Number: ISTLDG
Trading Properties
Minimum Order Quantity: 1 set
Price: USD200-800/ set
Payment Terms: T/T,Western Union
Supply Ability: 100 sets per day
Product Summary
DN200-400mm electromagnetic flow meter with PTFE/PFA/F46 liner, ±0.5% accuracy, 4-20mA output, and RS485/HART communication. Certified for -20°C~120°C fluids, supports custom electrodes and flange standards.

Product Details

Highlight:

PTFE Lined Electromagnetic Flowmeter

,

Electromagnetic Flow Meter 20mA

,

DN400 EMF Flow Meter

Caliber: DN200-400mm
Power Supply: AC220V,DC24V, 3.6V
Display: Instantaneous Flow, Total Flow, Flow Velocity
Structure Type: Integrate Or Remote
Pressure: 0.6Mpa-10Mpa
Accuracy: ±0.5% Of Reading
Fluid Temperature: -20°C~120°C
Ambient Temperature: -20℃~60℃
Environment Temperature: -10℃~+60℃
Output: 4-20mA
Communication: RS485 MODBUS RTU, HART, GPRS
Electrode: SS316L, Hastelloy B, Hastelloy C, Titannium, Tantanlum, Platinum-iridium
Flange Standard: DIN, ANSI, JIS
Product Description
Safety Electromagnetic Flow Meter 20mA PTFE PFA F46 Liner Material DN200-DN400 EMF Flow Meter
Product Overview

Safety Electromagnetic Flow Meter 20mA with PTFE/PFA/F46 Liner Material for DN200-DN400 pipe sizes. Designed for reliable flow measurement in industrial applications.

Common Problems and Solutions
  1. Flow Reading Fluctuates/Jumps (Most Common)
    Causes: Air bubbles in the pipe, insufficient pipe filling, poor grounding, electromagnetic interference
    • Air removal: Install at the low point of the pipeline or add an exhaust valve upstream
    • Full pipe: Install horizontally with electrodes on the side to avoid air accumulation at the top; install vertically with fluid flowing upward
    • Grounding: Use a dedicated ground wire with resistance <10Ω; install grounding rings for plastic/insulated pipes
    • Anti-interference: Route signal cables away from power cables and ground the shielding layer at one end only
  2. No Flow Reading/Zero Display
    Causes: Empty pipe, reversed wiring, excitation/electrode failure, incorrect parameters
    • Ensure the pipeline is fully filled with no negative pressure
    • Check for reversed excitation and signal wires
    • Verify parameters such as meter diameter, measuring range, and units
    • Measure excitation coil resistance (normal: 80-150Ω)
  3. Inaccurate Measurement (Over/Under Reading)
    Causes: Electrode fouling, damaged liner, insufficient straight pipe length, zero drift
    • Clean electrodes: Use a soft brush or dilute hydrochloric acid to remove insulating deposits
    • Inspect liner: Check for wear, bulges, or cracks
    • Straight pipe requirements: Upstream ≥10D, downstream ≥5D (D = pipe diameter)
    • Zero calibration: Perform zero calibration when the pipe is full and static
  4. Zero Drift/Negative Reading with Flow
    Causes: Poor grounding, contaminated electrodes, low medium conductivity, interference
    • Re-establish reliable grounding to ensure equipotential connection
    • Clean electrodes and check insulation
    • Confirm medium conductivity >5μS/cm
    • Keep away from strong interference sources such as inverters and motors
Routine Maintenance (Preventive Measures)
  • Clean electrodes regularly to prevent fouling coverage
  • Maintain full pipe condition with no air bubbles or negative pressure
  • Ensure reliable grounding, separate from motor/pipe grounding
  • Route signal and power cables separately
  • Perform zero calibration regularly (every 3-6 months)